BDZ52-32A220VIP55正泰元件帶漏電防爆斷路器
技術(shù)參數(shù)
防爆標(biāo)志:ExdeIIBT4/T5/T6、ExdeIICT4/T5/T6、DIP A20 TA,T4/T5/T6;
額定電壓:AC220/380V,非標(biāo)準(zhǔn)電壓:12V/24V/36V/127V/660V;
開(kāi)關(guān)電流:10A—800A;
防護(hù)等級(jí):IP54/IP55/IP65;
螺紋規(guī)格:DN15-DN100/G1/2-G4寸
引入線規(guī)格:直徑6mm-80mm;引出線規(guī)格:直徑6mm-80mm;
引入引出方向:上進(jìn)上出,下進(jìn)下出(可按客戶(hù)要求不受限制)
BDZ52-32A220VIP55正泰元件帶漏電防爆斷路器
BDZ52-10A/380V BDZ52-16A/380V BDZ52-20A/380V
BDZ52-25A/380V BDZ52-32A/380V BDZ52-40A/380V
BDZ52-50A/380V BDZ52-63A/380V BDZ52-80A/380V
BDZ52-100A/380V BDZ52-225A/380V BDZ52-250A/380V
BDZ52-400A/380V BDZ52-10A/220V BDZ52-16A/220V
BDZ52-20A/220V BDZ52-25A/220V BDZ52-32A/220V
BDZ52-40A/220V BDZ52-50A/220V BDZ52-63A/220V
BDZ52-80A/220V BDZ52-100A/220V BDZ52-225A/220V
BDZ52-250A/220V BDZ52-400A/220V BDZ52L-10A/380V BDZ52L-16A/380V
BDZ52L-20A/380V BDZ52L-25A/380V BDZ52L-32A/380V BDZ52L-40A/380V
BDZ52L-50A/380V BDZ52L-63A/380V BDZ52L-80A/380V
BDZ52L-100A/380V BDZ52L-225A/380VBDZ52L-250A/380V
BDZ52L-400A/380V BDZ52L-10A/220V BDZ52L-16A/220V BDZ52L-20A/220V
BDZ52L-25A/220V BDZ52L-32A/220V BDZ52L-40A/220V BDZ52L-50A/220V
BDZ52L-63A/220V BDZ52L-80A/220V BDZ52L-100A/220V BDZ52L-225A/220V
BDZ52L-250A/220V BDZ52L-400A/220V
防爆斷路器按防爆等級(jí)劃分可分為:ExdIIBT6/ExdIICT6
防爆斷路器一般有幾P?
2P\3P/4P
技術(shù)要求:
1)防爆箱產(chǎn)品須嚴(yán)格按照企業(yè)標(biāo)準(zhǔn)
2)裝配前應(yīng)對(duì)零、部件的主要配合尺寸進(jìn)行復(fù)查。
3)裝配過(guò)程中零件不允許磕、碰、劃傷防爆面。
4)螺釘和螺母緊固時(shí),嚴(yán)禁打擊或使用不合適的旋具和扳手。
5)裝配電氣部件前按要求進(jìn)行打壓試驗(yàn),加壓1MP,保持10-12S。應(yīng)保證箱體無(wú)明顯變形,無(wú)泄漏。
6)裝配電氣部件時(shí)注意位置恰當(dāng),安裝牢固。
7)線號(hào)使用打號(hào)機(jī)打號(hào),線號(hào)清晰完整。接線注意線序顏色及線徑。
8)電氣設(shè)備安裝后按電氣設(shè)計(jì)要求調(diào)試。
9)調(diào)試結(jié)束后緊固線束,裝好線槽蓋,注意接地線是否連接好。接地線可使用Φ20-30圓棒纏繞6-8圈,以減少其運(yùn)動(dòng)損傷。
10)緊固箱蓋前,于箱體防爆面均勻涂抹一層厚0.1-0.3mm3#鈣基脂。
11)緊固箱蓋時(shí),用18N.M擰緊力矩將各螺釘交叉、對(duì)稱(chēng)、逐步、均勻擰緊。
12)箱蓋緊固后應(yīng)使用塞規(guī)檢查隔爆縫隙,縫隙小于0.1mm。
13)裝配完成后清潔箱體表面,使用發(fā)泡塑料適度包裝,避免運(yùn)輸及安裝過(guò)程破壞箱體結(jié)構(gòu)及表面噴涂層。